A three-phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 1 mH/km per phase

A three-phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 1 mH/km per phase

Q. A three-phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 1 mH/km per phase, and the capacitance is 0.01 µF/km per phase. The line is under open circuit condition at the receiving end and energized with 400 kV at the sending end, the receiving end line voltage in […]

A three-phase 50 Hz, 400 kV transmission line is 300 km long. The line inductance is 1 mH/km per phase Read More »

A 220 V (line), three-phase, Y-connected, synchronous motor has a synchronous impedance of (0.25 + 𝑗2.5) Ω/phase

A 220 V (line), three-phase, Y-connected, synchronous motor has a synchronous impedance of (0.25 + 𝑗2.5) Ω/phase

Q. A 220 V (line), three-phase, Y-connected, synchronous motor has a synchronous impedance of (0.25 + 𝑗2.5) Ω/phase. The motor draws the rated current of 10 A at 0.8 pf leading. The rms value of line-to-line internal voltage in volts (round off to two decimal places) is Solution:

A 220 V (line), three-phase, Y-connected, synchronous motor has a synchronous impedance of (0.25 + 𝑗2.5) Ω/phase Read More »

A delta-connected, 3.7 kW, 400 V(line), three-phase, 4-pole, 50-Hz squirrel-cage induction motor has the following equivalent circuit parameters per phase referred

A delta-connected, 3.7 kW, 400 V(line), three-phase, 4-pole, 50-Hz squirrel-cage induction motor has the following equivalent circuit parameters per phase referred

Q. A delta-connected, 3.7 kW, 400 V(line), three-phase, 4-pole, 50-Hz squirrel-cage induction motor has the following equivalent circuit parameters per phase referred to the stator: 𝑅1 = 5.39 Ω, 𝑅2 = 5.72 Ω, 𝑋1 = 𝑋2 = 8.22 Ω. Neglect shunt branch in the equivalent circuit. The starting line current in amperes (round off to

A delta-connected, 3.7 kW, 400 V(line), three-phase, 4-pole, 50-Hz squirrel-cage induction motor has the following equivalent circuit parameters per phase referred Read More »

A 220 V DC shunt motor takes 3 A at no-load. It draws 25 A when running at full-load at 1500 rpm.

A 220 V DC shunt motor takes 3 A at no-load. It draws 25 A when running at full-load at 1500 rpm. The armature and shunt resistances are 0.5 Ω

Q. A 220 V DC shunt motor takes 3 A at no-load. It draws 25 A when running at full-load at 1500 rpm. The armature and shunt resistances are 0.5 Ω and 220 Ω, respectively. The no- load speed in rpm (round off to two decimal places) is                                       . Solution:

A 220 V DC shunt motor takes 3 A at no-load. It draws 25 A when running at full-load at 1500 rpm. The armature and shunt resistances are 0.5 Ω Read More »

A single-phase transformer of rating 25 kVA, supplies a 12 kW load at power factor of 0.6 lagging. The additional load at unity power factor in

A single-phase transformer of rating 25 kVA, supplies a 12 kW load at power factor of 0.6 lagging. The additional load at unity power factor in

Q. A single-phase transformer of rating 25 kVA, supplies a 12 kW load at power factor of 0.6 lagging. The additional load at unity power factor in kW (round off to two decimal places) that may be added before this transformer exceeds its rated kVA is                     . Solution:

A single-phase transformer of rating 25 kVA, supplies a 12 kW load at power factor of 0.6 lagging. The additional load at unity power factor in Read More »

The magnetic circuit shown below has uniform cross-sectional area and air gap of 0.2 cm. The mean path length of the core is 40 cm

The magnetic circuit shown below has uniform cross-sectional area and air gap of 0.2 cm. The mean path length of the core is 40 cm

Q. The magnetic circuit shown below has uniform cross-sectional area and air gap of 0.2 cm. The mean path length of the core is 40 cm. Assume that leakage and fringing fluxes are negligible. When the core relative permeability is assumed to be infinite, the magnetic flux density computed in the air gap is 1

The magnetic circuit shown below has uniform cross-sectional area and air gap of 0.2 cm. The mean path length of the core is 40 cm Read More »

The probability of a resistor being defective is 0.02. There are 50 such resistors in a circuit

The probability of a resistor being defective is 0.02. There are 50 such resistors in a circuit

Q. The probability of a resistor being defective is 0.02. There are 50 such resistors in a circuit. The probability of two or more defective resistors in the circuit (round off to two decimal places) is     . Solution: Probability of a resistor being defective (P) = 0.02 Number of resistors (n) = 50 Mean (λ)

The probability of a resistor being defective is 0.02. There are 50 such resistors in a circuit Read More »